If a CPI-enabled device is running and there are skipped scans in the data logger, what can be done?

The default CPI bus speed setting is 250 kB/s. The speed is adjustable in your CRBasic data logger program. Use the CPISpeed() instruction in your CRBasic program to adjust the CPI bus bandwidth to meet the following maximum combined (total) Ethernet cable lengths:

  • 1000 kB/s for maximum combined Ethernet cable lengths of 15.2 m (50.0 ft)
  • 500 kB/s for maximum combined Ethernet cable lengths of 61.0 m (200.0 ft)
  • 250 kB/s for maximum combined Ethernet cable lengths of 152.4 m (500.0 ft)

This was helpful

FAQs Home